Item(s) Added To Your Bag

Metravi PRO ERT-1602 Earth Resistance and Soil Resistivity Tester

Click To Zoom

Metravi PRO ERT-1602 Earth Resistance and Soil Resistivity Tester

Metravi PRO ERT-1602 Earth Resistance and Soil Resistivity Tester

(Based On 10 Reviews)

The Pro ERT-1602 features precision 4-wire, 3-wire and simple 2-wire measurement methods to measure Earth Resistance, Soil Resistivity, Earth Voltage and AC Voltage. Unlike other Earth Testers, you do not need to calculate Soil Resistivity as this instrument gives you the measurement directly.

Request Callback

Order In Bulk

Generate Quote

100% ORIGINAL Products Details

100% ORIGINAL Products

SECURE Payments Details

SECURE Payments

100% BUYER Protection Details

100% BUYER Protection

₹ 48,600.00

(GST inclusive price) i
  • Base Value: ₹ 41186.4
  • GST: (18) % ₹ 7413.6
  • Total Value ₹ 48600

₹48,600.00

( - 0% OFF )

Need Help ?

Our Client Care Managers Are On Call 24/7 To Answer Your Question.

Description

Key Features

  • Import FFT (fast Fourier transform) technology, and AFC (automatic frequency control) technology, with unique anti-interference ability and environmental adaptability to ensure high repeated test consistency.
  • The large LCD, white backlight, and bar graph make the readings clear at a glance.
  • Features USB interface with data upload function; storage data can be uploaded to the computer and can be saved and printed.
  • Audio-visual Alarm and Overload Protection.
  • Earth Resistance: Rated current change-pole method, measurement current 20mA Max
  • Soil Resistivity: Wenner 4-pole measurement; Voltage to Earth: Average rectifier
  • Earth Voltage: Average rectification (between P(S)-ES)
  • Test Frequency: 128Hz / 111Hz / 105Hz / 94Hz (AFC)
  • Short-circuit Test
  • Open-circuit Test Voltage
  • Interference Test
  • Auxiliary Earth Test
  • Line Voltage
  • Data Hold
  • Overflow Indication
  • USB Interface
  • Alarm function
  • Auto Power-off
  • Overload Protection

 

What's in the box?

  • Meter
  • 4 Earth Rods
  •  4 Standard Test Wires (Red 20m; Yellow: 10m; Green: 10m; Black:20m)
  • 2 Simple Test Wires (Red 1.6m; Black 1.6m) 
  • Special USB Communication Cable
  • Software CD
  • Hard Carrying Case 
  • User Manual

Rating & Reviews

4.5
(Based On 10 Reviews)

Rating

0

0

0

0

0

Product Specifications

General Specification
Earth Resistance(R)Range: 0.00Ω~30.00ΩResolution: 0.01ΩAccuracy: ±2%rdg±3dgt
Range: 30.0Ω~300.0ΩResolution: 0.1ΩAccuracy: ±2%rdg±3dgt
Range: 300Ω~3000ΩResolution: 1ΩAccuracy: ±2%rdg±3dgt
Range: 3.00kΩ~30.00kΩResolution: 10ΩAccuracy: ±2%rdg±3dgt
Earth VoltageRange: 0.0~600V ACResolution: 0.1VAccuracy: ±2%rdg±3dgt
Soil Resistivity (ρ)
(ρ=2πaR, a:1 m-100m, π=3.14)
Range: 0.00Ωm~99.99ΩmResolution: 0.01ΩmAccording to the precision of R
Range: 100.0Ωm~999.9Ωm Resolution: 0.1Ωm
Range: 1000Ωm~9999ΩmResolution: 1Ωm
Range: 10.00kΩm~99.99kΩmResolution: 10Ωm
Range: 100.0kΩm~999.9kΩmResolution: 100Ωm
Range: 1000kΩm~9000kΩmResolution: 1kΩm
Measuring MethodEarth Resistance: Rated current change-pole method, measurement current 20mA Max
Soil Resistivity: Wenner 4-pole measurement; Voltage to Earth: Average rectifier
Earth Voltage: Average rectification (between P(S)-ES)
Test Frequency128Hz / 111Hz / 105Hz / 94Hz (AFC)
Short-circuit Test CurrentAC 20mA maxOpen-circuit Test VoltageAC 40V max
Data Storage300 groupsTest Voltage WaveSine wave
Electrode Distance RangeCan be set 1m-100mWeight4.5kg (with package) 
Data AccessData read function: “READ” symbol display
Data HoldData hold function: “HOLD” symbol display
Overflow IndicationExceed measurement range overflow function: “OL” symbol display
LCD DimensionLCD Frame Dimension:128mm×75mm; LCD Window Dimension: 124mm×67mm
Tester Dimension212mm(L) × 175mm(W) × 76mm(H)
Testing WiresRed 20m, Black 20m, Yellow 10m, Green 10m, Red 1.6m, Black 1.6m (Total 6pcs)
Auxiliary Earth Rod4 PCS: Φ10mm×150mm
USB InterfaceIf measured value exceeds set alarm value, alarm goes “toot-toot-toot”.
Alarm Function Measuring value exceeds alarm setting value, will “Toot-toot-toot” alarm hint
Auto Power-off15 Minutes after power on, will automatic power off without any operation 
Overload ProtectionEarth Resistance: between each interfaces of C(H)-E, P(S)-ES, AC 280V/3 seconds
Interference TestAutomatic recognition of interference signal, interference voltage higher than 5V will display “ ”
symbol
Auxiliary Earth TestWith auxiliary earth resistance test function: 0.00KΩ-30kΩ (100R+rC<50kΩ, 100R+rP<50kΩ
Line VoltageMeasure voltage to ground, AC voltage: AC 600V Max
Battery VoltageWhile battery voltage decreases to around 7.5V, will display low battery voltage symbol “ ”,
and remind to replace the battery
Working CurrentSystem Standby: around 20mA (Backlight shut off); Power on: 45mA (backlight shut off at
25mA); Measurement:100mA (Backlight shut off)
Withstand VoltageOver 20MΩ (between circuit and enclosure it is 500V)
Electromagnetic FeaturesIEC61326 (EMC)
Suitable Safety Standard IEC61010-1 (CAT III 300V, CAT IV 150V, Pollution 2), IEC61010-031, IEC61557-1 (Earth
resistance), IEC61557-5 (Soil resistivity), JJG 366-2004
PowerDC 9V (Alkaline dry battery R14S 1.5V 6 PCS, continuous standby for 300 hours)
WeightMeter 950g, Test Wires 1560gms, Auxilliary Ground Rods (4 nos) 935g
Working Temperature &
Humidity
-10°C-40°C, below 80%RH
Storage Temperature &
Humidity
-20°C-60°C, below 70%RH