Item(s) Added To Your Bag

Metravi PRO IRC-600 Digital TRMS AC Clamp Meter with IR Thermometer

Click To Zoom

Metravi PRO IRC-600 Digital TRMS AC Clamp Meter with IR Thermometer

Metravi PRO IRC-600 Digital TRMS AC Clamp Meter with IR Thermometer

(Based On 10 Reviews)

The Metravi PRO IRC-600 Digital TRMS AC Clamp Meter with Infrared Thermometer provides fast A/D converting sampling time, high accuracy, TRMS measurements and also offers all needed features for measurements, including Non-contact Voltage Detector and a built-in Infrared Thermometer!

Request Callback

Order In Bulk

Generate Quote

100% ORIGINAL Products Details

100% ORIGINAL Products

SECURE Payments Details

SECURE Payments

₹ 11,178.00

(GST inclusive price) i
  • Base Value: ₹ 9472.9
  • GST: (18) % ₹ 1705.1
  • Total Value ₹ 11178

₹11,178.00

( - 0% OFF )

Need Help ?

Our Client Care Managers Are On Call 24/7 To Answer Your Question.

Description

Key Features

  • Low Pass Filter (VFD)
  • Accuracy: ±(0.8% + 4 digits)
  • TRMS AC Voltage: 6V / 60 / 600 / 1000V
  • Accuracy: ±(1.5% + 5 digits)
  • TRMS AC Current: 60A / 600A
  • Accuracy: ±(2.5% + 10 digits)
  • Resistance: 600Ω / 6kΩ / 60 / 600/ 6MΩ / 60MΩ
  • Accuracy: ±(1.5% + 6 digits)
  • K-type Temperature: 1000ºC/ 1832ºF
  • Accuracy: ±(1.0%+3d)
  • Infrared Temperature: -30 ~ 350 ºC/ -22 ~662ºF
  • Accuracy: ±1.5%±1ºC/1.8°F
  • IR Optical Resolution / Distance to Sighting Ratio: 4:1
  • Capacitance: 999.9nF / 9.999µF / 99.99 / 999.9/ 9.999mF / 99.99mF
  • Accuracy: ±(4% + 6 digits)
  • Frequency: 10kHz
  • Accuracy: ±(1.5% + 6 digits)
  • Continuity: Buzzer sounds at 50Ω
  • Diode Test: Test Current <0.5mA MAX 3V
  • MAX/MIN
  • Data Hold

 

What's in the box?

  • Carrying Case
  • Silicon Test Leads
  • K-type Thermocouple 
  • Thermocouple Adaptor
  • User Manual
  • Batteries 

Rating & Reviews

4.5
(Based On 10 Reviews)

Rating

0

0

0

0

0

Product Specifications

General Specification
Clamp SizeOpening 1.3" (33mm) approx.
TRMSThe AC Voltage and AC Current of this instrument are measured by TRMS, True RMS measurement is different from mean measurement.
The mean measurement method can only measure the symmetric waveform, such as sine wave.
True RMS measurements can reliably measure any irregular waveform and obtain valid values for AC voltage or AC current.
Diode TestTest current of 0.3mA typical;
Open circuit voltage 3.2V DC typical.
Continuity CheckThreshold <500; Test current < 0.5mA
Low Pass FilterVFD Measurements
Low Battery Indication"+" is displayed
Overrange Indication"OL" is displayed
Measurements Rate2 per second. Nominal ≥10ΜΩ (VDC
Input Impedanceand VAC)
Display6000 counts LCD
AC Current50 to 60Hz (AAC)
AC Voltage Bandwidth50 to 1000Hz (VAC)
Operating Temperature5 to 40°C (41 to 104°F)
Storage Temperature-20 to 60°C (-4 to 140°F)
Operating HumidityMax 80% up to 31°C (87°F) decreasing linearly to 50% at 40°C (104°F)
Storage Humidity<80%RH
Operating Altitude2000 meters (7000ft.) maximum.

 

Technical Specification
FunctionRangeResolutionAccuracy
DC Current60A 0.01A±(2.8% + 8 digits)
600A0.1A ±(2.8% + 5 digits)
AC Current (T-RMS)60A0.01A±(1.5% + 10 digits)
600A0.1A
DC Voltage600mV 0.1mV ±(0.8% + 4 digits)
6V0.001V±(1.2% + 5 digits)
60V0.01V
600V0.1V
1000V 1V
AC Voltage (T-RMS)6V0.001V±(1.5% + 5 digits)
60V 0.01V
600V0.1V
1000V 1V
Resistance600Ω0.1Ω ±(1.5% + 6 digits)
6kΩ0.001kΩ±(2.0% + 5 digits)
60kΩ0.01kΩ
600kΩ 0.1kΩ
6MΩ0.001MΩ±(2.8% + 10 digits)
60MΩ0.01MΩ
Capacitance999.9nF0.1nF±(4% + 6 digits)
9.999μF0.001μF
99.99μF 0.01μF
999.9μF0.1μF
9.999mF 0.001mF±(6% + 15 digits)
99.99mF0.01mF
Frequency5 to 9.999Hz0.001Hz±(1.5% + 6 digits)
99.99Hz0.01Hz
999.9Hz0.1Hz
9.999kHz0.001kHz
Duty Cycle 20.0% to 80.0% 0.1%±(1.2% + 5 digits)
Type-K Temp-20.0° to 1000°C0.1°C±(3% + 3°C)
4.0° to 1800°F0.1°F ±(3% + 6°F)
Infrared Temperature-30.0° to 350.0°C0.1°C±3°C at -30 to 0°C 
±2.0% or ±2°C at 0 to 350°C 
-22.0° to 662.0°F0.1°F±5°F at -22 to 32°F 
±2.0% or ±4°F at 32 to 662°F

Rating & Reviews

4.5
(Based On 10 Reviews)

Rating

0

0

0

0

0